Item - Relay
Voltage Sensing Relay
Input or Control Voltage
12V DC
DC Contact Rating - Relay
5A @ 12V
Item
Voltage Sensing Relay
Body Width - Relay
0.69 in
Overall Height - Relay
3.65 in
Body Depth - Relay
2.84 in
Body Height - Relay
3.54 in
Maximum Switching Current
5 A
Monitored Parameters
Overcurrent, Undercurrent
Maximum Switching Capacity
1,250 VA
Minimum Switching Current
10 mA
Contact Rating (DC)
5 A @ 12V
Maximum Switching Voltage
250V AC/DC
Maximum Operating Temperature
158 Degrees F
Minimum Operating Temperature
-40 Degrees F
Standards
C-Tick, CSA Certified, EN/IEC 60255-6, GL, GOST, UL Listed
Mechanical Operating Durability
30,000,000
[Us] Rated Supply Voltage
12 V DC +/- 10 %
Ambient Air Temperature For Operation
-20-50°C
Pollution Degree
3 IEC 60664-1
Connections - Terminals
screw terminals, 1 x 0.5...1 x 4 mm² AWG 20...AWG 11) solid without cable end || screw terminals, 2 x 0.5...2 x 2.5 mm² AWG 20...AWG 14) solid without cable end || screw terminals, 1 x 0.2...2 x 2.5 mm² AWG 24...AWG 12) flexible with cable end || screw terminals, 2 x 0.2...2 x 1.5 mm² AWG 24...AWG 16) flexible with cable end
Product Certifications
CSA || C-tick || GL || UL || GOST
Non-Dissipating Shock Wave
4 kV IEC 60255-5 || 4 kV IEC 60664-1 || 4 kV IEC 61000-4-5
Relay Monitored Parameters
overvoltage or undervoltage detection || self-powered
Switching Capacity In Va
1250 VA
Electrical Durability
100000 cycles
Ip Degree Of Protection
IP20 IEC 60529 terminals) || IP30 IEC 60529 casing)
Tightening Torque
0.6-1 N.m IEC 60947-1
Polarity
non reversible polarity on DC supply
Electromagnetic Compatibility
emission standard for industrial environments EN/IEC 61000-6-4 || emission standard for residential, commercial and light-industrial environments EN/IEC 61000-6-3 || immunity for industrial environments NF EN/IEC 61000-6-2
Immunity To Microbreaks
20 ms 12 V
Measurement Range
9...15 V voltage DC
Utilisation Category
AC-12 IEC 60947-5-1 || AC-13 IEC 60947-5-1 || AC-14 IEC 60947-5-1 || AC-15 IEC 60947-5-1 || DC-12 IEC 60947-5-1 || DC-13 IEC 60947-5-1 || DC-14 IEC 60947-5-1
Operating Rate
u003c= 360 operations/hour full load
Time Delay Type
adjustable 0.1...10 s, 0 + 10 % on crossing the threshold
Reset Time
1500 ms time delay
Dielectric Test Voltage
2 kV AC 50 Hz, 1 min IEC 60255-5 || 2 kV AC 50 Hz, 1 min IEC 60664-1
Relative Humidity
95-95 % 55-55°C IEC 60068-2-30
Repeat Accuracy
+/- 0.5 % input and measurement circuit || +/- 1 % time delay
Measurement Accuracy
+/- 10 % of the full scale value
Housing Material
self-extinguishing plastic
Mechanical Durability
30000000 cycles
Overvoltage Category
III IEC 60664-1
Supply Voltage Limits
7-20 V DC
Insulation Resistance
u003e 500 MOhm 500 V DC IEC 60255-5 || u003e 500 MOhm 500 V DC IEC 60664-1
Hysteresis
5-20 % threshold setting
[Ui] Rated Insulation Voltage
250 V IEC 60664-1 || 400 V IEC 60664-1
Relay Type
voltage control relay
Run-Up Delay At Power-Up
1000 ms DC
Contacts Type And Composition
1 C/O
Product Or Component Type
voltage control relay
Measurement Error
u003c 1 % over the whole range with voltage variation || 0.2 %/°C with temperature variation
Mounting Support
35 mm symmetrical DIN rail conforming to EN/IEC 60715
Maximum Power Consumption In W
1 W DC
Local Signalling
for power ON LED (green) || for relay ON LED (yellow)
Ambient Air Temperature For Storage
-40-70°C
Vibration Resistance
0.35 mm 5-57.6 Hz)IEC 60068-2-6 || 1 gn 57.6-150 Hz)IEC 60255-21-1
Product Specific Application
for single-phase and DC supply
Operating Position
any position without derating
Shock Resistance
5 gn IEC 60068-2-27
Country of Origin (subject to change)
Indonesia