Full Load Amps-Inductive
50 A
Full Load Amps-Resistive
70 A
Standards
REACH Art 33, WEEE (2012/19/EU)
Aux. Contact Configuration
1NO/1NC
Frame / Series / Class / Code
S2
Auxiliary Contact Form
1NO/1NC
Rated operating power with AC-3, 400 V
22 kilowatt
Rated current [In] for the power loss specification
51 ampere
Max. rated AC voltage for controls, 50 Hz
230 volt
Rated operating current Ie with AC-3, 400 V
51 ampere
Power loss per pole, current-dependent [PlIp]
4 watt
Number of making contacts and main contacts
3
suitable for series installation
Yes
Power loss, static, current-independent [Pls]
16 watt
Connection type
Screw connection
rated operational power AC-1 at 400 V
46 kilowatt
Horsepower @ Single Phase - 240V AC
10 hp
Mounting Hole Distance - Height
3.84 in
Mounting Hole Diameter
0.2 in
Horsepower @ Three Phase - 600V AC
50 hp
Maximum Voltage Rating
690V AC
Terminal Connection Type
Screw Terminals
Includes Auxiliary Contacts
Yes
Mounting Style
DIN Rail, Surface
Horsepower @ Three Phase - 208V AC
15 hp
Horsepower @ Three Phase - 480V AC
40 hp
Mechanical Operating Durability
10,000,000
Number of Normally Open Main Contacts
3
Horsepower @ Single Phase - 120V AC
3 hp
Horsepower @ Three Phase - 240V AC
15 hp
Full Load Current - Resistive
70 A
Embedded Surge Suppressor
No
Reversing Capability
Non-Reversing
Maximum Operating Temperature
140 Degrees F
Response Time
10 to 18 msec (AC Operation Opening Delay Operating Times for 0.8 ... 1.1 x Us1), 10 to 18 msec (AC Operation Opening Delay Operating Times for 1.0 x Us1), 10 to 80 msec (AC Operation Closing Delay Operating Times for 0.8 ... 1.1 x Us1), 12 to 22 msec (AC Operation Closing Delay Operating Times for 1.0 x Us1)
Number of Auxillary Contacts
2
Minimum Operating Temperature
-13 Degrees F
Mounting Hole Distance - Width
1.77 in
Full Load Current - Inductive
51 A
NEMA Enclosure Rating
No Enclosure
Country of Origin (subject to change)
Germany