Item
Power Distribution Block
Voltage Rating
1000V AC/DC
Wire Range
14 AWG to 2 AWG, 14 AWG to 2/0 AWG
Features
All sizes have optional adder poles for increased flexibility and ease-of-use. Adder poles allow for customization of primary and secondary wire combinations.
Fuse UL Class
UL1953 Open-style
Max. Operating Temp.
80 deg C
APPROVALS u0026 STANDARDS
UL Listed to subject 1953, File E352417 unless noted otherwise; CSA Certified Class 6228 01
Short Circuit Rating (Class CC)
30 kA
Short Circuit Rating (Class RK5)
30 kA
Short Circuit Rating (Class RK1)
100 kA
Number of Openings per Pole (Primary)
1
Short Circuit Rating (Class J)
200 kA
Short Circuit Rating (Class L)
200 kA
Connector Material
Tin-plated Aluminum
Hex/Screw Size u0026 Type (Primary)
7/16-20 x .55
Short Circuit Rating (Class T)
200 kA
Short Circuit Rating (Standalone)
10 kA
Short Circuit Rating (Class G)
60 kA
Hex/Screw Size u0026 Type (Secondary)
5/16-24 x .38
Mounting Hole Dia.
0.44 in
Country of Origin (subject to change)
Mexico