Item
Power Distribution Block 600V 335A Tlb
Primary Connections/Pole
1
Primary Wire Range (AWG)
AWG 4 to 600 kcmil (Copper or Aluminium)
Secondary Connection/Pole
8
Secondary Wire Range (AWG)
AWG 14 to AWG 2 (Copper or Aluminium)
Power Distribution Block Design
Open
Standards
CE; UL Recognized E60616 CCN XCFR2; CSA File 70361 Class 6228 01
For Conductor Material
Aluminum, Copper
Terminal Material
Aluminum
For Line Copper Wire Size - Minimum
4 AWG
For Line Copper Wire Size - Maximum
600 kcmil
For Line Aluminum Wire Size - Maximum
600 kcmil
For Load Copper Wire Size - Minimum
14 AWG
For Line Aluminum Wire Size - Minimum
4 AWG
Maximum Operating Temperature
302 Degrees F
For Load Copper Wire Size - Maximum
2 AWG
For Load Aluminum Wire Size - Maximum
2 AWG
Line Side Connection Type
Lug
Load Side Connection Type
Lug
For Load Aluminum Wire Size - Minimum
14 AWG
Maximum Current - Copper Conductor
335 A
Maximum Current - Aluminum Conductor
270 A
Maximum Voltage
600 V AC/DC
Line Side Wire Size Range
4 AWG - 600 kcmil
Load Side Wire Range
14 AWG - 2 AWG
Amps
Al conductor: 270 A; Cu Conductor: 335 A
Electrical Connection
Tin plated Aluminium Lugs
Wire Strip Length
Line 1.06 in; Load 0.56 in top; Load 1 in bottom
Short Circuit Current Rating
65 kA
Max. Operating Temp.
302°F
Min. Operating Temp.
-40°F
Wire Stripping Length
line: 1.06 in, load: 0.56 in for top connection, load: 1 in for bottom connection
Ambient Air Temperature For Operation
-40-302°F
[Ics] Rated Service Breaking Capacity
100 kA UL 508 A
Line Rated Current
335-335 A copper, 270-270 A aluminium
Product Compatibility
9080LB42
Connections - Terminals
load lug 45 lbf.in AWG 6...AWG 4 copper or aluminium, load lug 40 lbf.in AWG 8 copper or aluminium, load lug 50 lbf.in AWG 2 copper or aluminium, line lug 275 lbf.in AWG 6...400 kcmil copper or aluminium, load lug 35 lbf.in AWG 14...AWG 10 copper or aluminium
Number of Cables
line 1 , AWG 4...600 kcmil, copper or aluminium, load 8 , AWG 14...AWG 2, copper or aluminium
Product or Component Type
Power Distribution Block
Number of Terminals
1 line, 8 load
Country of Origin (subject to change)
United States