Item - Plugs and Receptacles
Locking Plug
Shrouded / Non-Shrouded
Non-Shrouded
Grade - Plugs and Receptacles
Marine
Amps - Plugs and Receptacles
20
NEMA Plug Configuration - Plugs and Receptacles
L5-20P
Voltage - Plugs and Receptacles
125V AC
Special Features
Corrosion resistant
Cord Size
0.360 in to 0.930 in
Standards
CSA Certified C22.2 No. 42, Federal Specification W-C-596, UL 498
Color - Plugs and Receptacles
Yellow
Application
Extra Heavy Duty Industrial
Wire Connection Type
Screw Terminals
Maximum Operating Temperature
75 Degrees C
Voltage Rating
125/250V AC
Minimum Operating Temperature
-40 Degrees C
For Maximum Cable Diameter
0.93 in
UL 94 Flammability Rating
HB
Resistance Properties
Chemical Resistant, Corrosion Resistant, Impact Resistant
NEMA Plug Configuration
L5-20P
For Minimum Cable Diameter
0.36 in
Blade Material
Nickel-Plated Brass
Connection Orientation
Straight
Temp. Rise
Max 30C Temp. Rise at full rated current after 50 cycles of overload at 150% of rated current at a power factor of .75.
Flammability
HB or better per UL94 or CSA 22.2 No. 0.6
Wire Size
#16 AWG to #8 AWG
Operating Temp.
Maximum Continuous 75 C Minimum -40 C (w/o impact)
Environmental Conditions
Indoor Dry Unless Protected By Additional Means
Cord Type
All Listed Portables
Dielectric Strength
Withstands 2,000V minimum
Current / Amperage Rating
20 A
Material - Mounting Hardware
Cord Mounted
OEM Brand Name
Hubbell Wiring Device-Kellems
Cable Range
0.360 - 0.930 in
Operating Temperature
Maximum continuous 75°C and minimum -40°C without Impact
Industry Standard(s)
Certified to CSA C22.2 No.42nFed.Spec. W-C-596nListed to UL 498
Display Size
Standard Sized
Voltage Rating Description
125/250 VAC
Item Type
20A Corrosion Resistant Insulgrip® Plug
Connectivity
Pressure Terminal Screws
Dimensions
2.26 in x 2.26 in x 2.75 in
Performance
Electrical - Current Interrupting - Certified for current interrupting at full rated currentnElectrical - Dielectric Voltage - Withstands 2,000V minimumnEnvironmental - Flammability - HB or better per UL94 or CSA 22.2 No. 0.6nEnvironmental - Moisture Resistance - IP20 SuitabilitynEnvironmental - Operating Temperatures - Maximum Continuous 75°C Minimum -40°C (w/o impact)nMechanical - Terminal Accommodation - #16 AWG - #8 AWG stranded copper wire only.nMechanical - Terminal Identification - Terminals identified in accordance with UL 498
Country of Origin (subject to change)
United States