Protection Method
Nonfusible
HP
10 hp @ 480V AC, 15 hp @ 600V AC, 5 hp @ 240V AC
Neutral Assembly Included
No
Fusible / Nonfusible
Nonfusible
Standards
CCC, CSA Certified, EAC, IEC, Marine, UL Listed
Features
Opening for 6 mm (0.24 in) Shaft Width
For Fuse Class
Not Applicable
Housing Material
Non-Metallic
Resistance Properties
Fire-Resistant
Horsepower @ 480V AC
10 hp
Standard Conduit Size
0.75 in
Horsepower @ 600V AC
15 hp
Fire Resistance
960°C IEC 60695-2-1
Connections - Terminals
power circuit screw clamp terminals 10-10 mm² solid || power circuit screw clamp terminals 6-6 mm² flexible - with cable end
Intermittent Duty Class
30
Contacts Type And Composition
3 NO
Tightening Torque
power circuit 2.1-2.1 N.m screw clamp terminals
Rated Conditional Short-Circuit Current
10 kA 400 V 50 A aM || 10 kA 400 V 50 A gG
Electrical Durability
100000 cycles AC-21 || 30000 cycles DC-1...5
Breaking Capacity
320 A 400 V AC-21A) || 320 A 400 V AC-22A) || 320 A 400 V AC-23A)
[Ie] Rated Operational Current
29 A AC-23 Ue: 400 V
Rated Operational Power In W
11 kW 400...415 V AC-3) || 11 kW 690 V AC-3) || 15 kW 500 V AC-3) || 15 kW 690 V AC-23A) || 18.5 kW 500 V AC-23A) || 5.5 kW 230...240 V AC-3) || 7.5 kW 230...240 V AC-23A) || 15 kW 400...415 V AC-23A)
[Ithe] Conventional Enclosed Thermal Current
32 A
Making Capacity
400 A 400 V AC-21A || 400 A 400 V AC-22A || 400 A 400 V AC-23A
Mounting Support
plate || symmetrical rail
Network Frequency
50/60 Hz
[Ue] Rated Operational Voltage
690 V AC 50/60 Hz
Performance Level
high performance
[Icm] Rated Short-Circuit Making Capacity
1 kA 400 V at Ipeak
Suitability For Isolation
yes
[Ith] Conventional Free Air Thermal Current
40 A
Ip Degree Of Protection
IP20 conforming to IEC 60529
Mechanical Robustness
vibrations 10...150 Hz 1 gn) IEC 60068-2-6 || shocks 11 ms 30 Gn) IEC 60068-2-27
Product Certifications
UL || CSA || GL || UKCA || CCC
Product Or Component Type
switch body
Ambient Air Temperature For Operation
-20-50°C
[Uimp] Rated Impulse Withstand Voltage
8 kV
[Icw] Rated Short-Time Withstand Current
480 A 400 V 1 s
Mechanical Durability
100000 cycles
IEC Terminal Connection
Power circuit screw clamp terminals 0.02 in² (10 mm²) solid; Power circuit screw clamp terminals 0.01 in² (6 mm²) flexible - with cable end
Iec Rated Operational Power in W
11 kW 400 to 415 V AC-3); 11 kW 690 V AC-3); 15 kW 500 V AC-3); 15 kW 690 V AC-23A); 18.5 kW 500 V AC-23A); 5.5 kW 230 to 240 V AC-3); 7.5 kW 230 to 240 V AC-23A); 15 kW 400 to 415 V AC-23A)
Rated Conditional Short Circuit Current
10 kA 400 V 50 A aM; 10 kA 400 V 50 A gG
Country of Origin (subject to change)
Czechia