Protection Method
Nonfusible
HP
10 hp @ 480V AC, 10 hp @ 600V AC, 5 hp @ 240V AC
Fusible / Nonfusible
Nonfusible
Neutral Assembly Included
No
Standards
CCC, CSA Certified, EAC, IEC, Marine, UL Listed
Features
Opening for 6 mm (0.24 in) Shaft Width
Product Type
Load Break Switch
Horsepower @ 600V AC
10 hp
Standard Conduit Size
0.75 in
For Fuse Class
Not Applicable
Resistance Properties
Fire-Resistant
Housing Material
Non-Metallic
Horsepower @ 480V AC
10 hp
Rated Conditional Short-Circuit Current
10 kA 400 V 35 A aM || 10 kA 400 V 35 A gG
Mechanical Robustness
vibrations 10...150 Hz 1 gn) IEC 60068-2-6 || shocks 11 ms 30 Gn) IEC 60068-2-27
[Ue] Rated Operational Voltage
690 V AC 50/60 Hz
Performance Level
high performance
Connections - Terminals
power circuit screw clamp terminals 10-10 mm² solid || power circuit screw clamp terminals 6-6 mm² flexible - with cable end
[Uimp] Rated Impulse Withstand Voltage
8 kV
Making Capacity
320 A 400 V AC-21A || 320 A 400 V AC-22A || 320 A 400 V AC-23A
[Icw] Rated Short-Time Withstand Current
384 A 400 V 1 s
Ip Degree Of Protection
IP20 conforming to IEC 60529
Contacts Type And Composition
3 NO
[Ithe] Conventional Enclosed Thermal Current
25 A
Mounting Support
symmetrical rail || plate
Suitability For Isolation
yes
Ambient Air Temperature For Operation
-20-50°C
Network Frequency
50/60 Hz
Breaking Capacity
250 A 400 V AC-21A) || 250 A 400 V AC-22A) || 250 A 400 V AC-23A)
[Ie] Rated Operational Current
21.8 A AC-23 Ue: 400 V
Intermittent Duty Class
30
[Icm] Rated Short-Circuit Making Capacity
1 kA 400 V at Ipeak
Rated Operational Power In W
11 kW 500 V AC-23A) || 15 kW 690 V AC-23A) || 1.5 kW 230...240 V AC-3) || 7.5 kW 500 V AC-3) || 7.5 kW 690 V AC-3) || 5.5 kW 230...240 V AC-23A) || 11 kW 400...415 V AC-23A) || 7.5 kW 400...415 V AC-3)
Product Certifications
UL || CSA || GL || UKCA || CCC
[Ith] Conventional Free Air Thermal Current
32 A
Product Or Component Type
switch body
Mechanical Durability
100000 cycles
Fire Resistance
960°C IEC 60695-2-1
Electrical Durability
100000 cycles AC-21 || 30000 cycles DC-1...5
Tightening Torque
power circuit 2.1-2.1 N.m screw clamp terminals
Country of Origin (subject to change)
Czechia