Item
IEC Magnetic Contactor
Full Load Amps-Inductive
50 A
Full Load Amps-Resistive
80 A
HP @ 1 Phase - 240V
7 1/2 hp
Aux. Contact Configuration
1NO/1NC
Standards
CSA C22.2 No 14, EN 60947-4-1, EN 60947-5-1, IEC 60947-4-1, IEC 60947-5-1, UL 508, IEC 60335-1, UL, CSA, RINA, GOST, CCC, DNV, LROS, GL, BV, UKCA, TH IEC 60068-2-30
Application
Motor Control, Resistive Load
Features
Without Built-In Suppressor Module; Preassembled with Reversing Power Busbar
Switching Voltage
17 V (Signalling Circuit)
Working Height
Up to 9842.52 ft
Mechanical Durability
6 Mcycles
Electrical Durability
1.45 Mcycles (50 A, AC-3, Less than 440 V); 1.1 Mcycles (80 A, AC-1, Less than 440 V)
Includes Protective Cover
Yes
Max. Operating Watts
15 kW (at 220 to 230V AC 50 Hz), 22 kW (at 380 to 400V AC 50 Hz), 30 kW (at 500V AC 50 Hz), 33 kW (at 660 to 690V AC 50 Hz), 25 kW (at 415V AC 50 Hz), 30 kW (at 440V AC 50 Hz)
Vibration Resistance
4 G (Contactor Closed), 2 G (Contactor Open)
Electrical Connection
Control Circuit: Screw Clamp Terminals, Power Circuit: EverLink BTR Screw Connectors
Shock Resistance
15 G for 11 ms (Contactor Closed), 10 G for 11 ms (Contactor Open)
Rated Making Capacity
140 A (AC Signalling Circuit), 250 A (DC Signalling Circuit), 900 A @ 440V (Power Circuit)
Operating Time
4 to 19 ms (Opening), 12 to 26 ms (Closing)
Rated Short-Time Withstand Current
400 A (at 40°C for 10 s Power Circuit), 810 A (at 40°C for 1 s Power Circuit), 84 A (at 40°C for 10 min Power Circuit), 208 A (at 40°C for 1 min Power Circuit), 100 A (For 1 s Signalling Circuit), 120 A (For 500 ms Signalling Circuit), 140 A (For 100 ms Signalling Circuit)
Impulse Withstand Voltage
6 kV
Rated Insulation Volts
600/690V
Rated Breaking Capacity
900 A @ 440V
Signalling Circuit Frequency
25 to 400 Hz
Rated Voltage
690V AC, 300V DC
Overvoltage Category
CAT III
Switching Current
5 mA (Signalling Circuit)
Fuse Amps
10 A (Signalling Circuit), 100 A (Type 1 Power Circuit), 100 A (Type 2 Power Circuit)
Thermal Amperage
10 A (at 60°C Signalling Circuit), 80 A (at 60°C Power Circuit)
Environmental Attributes
Mercury Free, PVC Free, Toxic Heavy Metal Free, Pollution Degree 3
Control Circuit Voltage Limits
Drop-Out AC: 0.3 to 0.6 Uc (at -40 to 70°C 60 Hz) , Operational AC: 0.85 to 1.1 Uc (at -40 to 60°C 60 Hz), 1 to 1.1 Uc (at 60 to 70°C 60 Hz)
Tightening Torque
1.7 Nm (Control Circuit), 2.5 to 8 Nm (Power Circuit)
Operating Speed
3600 cycles per hr
Insulation Resistance Range
Greater Than 10 MOhms (Signalling Circuit)
Auxiliary Contacts Type
Mechanically linked 1 NO + 1 NC IEC 60947-5-1; Mirror contact 1 NC IEC 60947-4-1
Motor Power HP
3 hp at 115 V AC 60 Hz for 1 phase motors; 7.5 hp at 230/240 V AC 60 Hz for 1 phase motors; 15 hp at 200/208 V AC 60 Hz for 3 phase motors; 15 hp at 230/240 V AC 60 Hz for 3 phase motors; 40 hp at 460/480 V AC 60 Hz for 3 phase motors; 40 hp at 575/600 V AC 60 Hz for 3 phase motors
Auxiliary Contact Composition
1 NO + 1 NC
Rated Insulation Voltage
Power circuit 690 V IEC 60947-4-1; Power circuit 600 V CSA; Power circuit 600 V UL; Signalling circuit 690 V IEC 60947-1; Signalling circuit 600 V CSA; Signalling circuit 600 V UL
IRMS Rated Making Capacity
140 A AC for signalling circuit conforming to IEC 60947-5-1; 250 A DC for signalling circuit conforming to IEC 60947-5-1; 900 A at 440 V for power circuit conforming to IEC 60947
Safety Reliability Level
B10d = 1369863 cycles contactor with nominal load EN/ISO 13849-1; B10d = 20000000 cycles contactor with mechanical load EN/ISO 13849-1
Rated Operational Current
50 A (at Less than 140°F (60°C)) at Less than or Equal to 440 V AC AC-3 for power circuit; 80 A (at Less than 140°F (60°C)) at Less than or Equal to 440 V AC AC-1 for power circuit; 50 A (at Less than 140°F (60°C)) at Less than or Equal to 440 V AC AC-3e for power circuit
Insulation Resistance
Greater than 10 MOhm for signalling circuit
Rated Impulse Withstand Voltage
6 kV IEC 60947
Product Certifications
UL; CSA; RINA; GOST; CCC; DNV; LROS (Lloyds register of shipping); GL; BV; UKCA
Hold-In Power Consumption in VA
13 VA 60 Hz cos phi 0.3 (at 68°F (20°C))
Interlocking Type
Mechanical
IP Degree Of Protection
IP20 front face IEC 60529
Average Impedance
1.5 mOhm - Ith 80 A 50 Hz for power circuit
Power Dissipation Per Pole
3.7 W AC-3; 9.6 W AC-1; 3.7 W AC-3e
Coil Technology
Without built-in suppressor module
Connections - Terminals
Control circuit screw clamp terminals 1 0.00 to 0.01 in² (1 to 4 mm²)flexible without cable end; Control circuit screw clamp terminals 2 0.00 to 0.01 in² (1 to 4 mm²)flexible without cable end; Control circuit screw clamp terminals 1 0.00 to 0.01 in² (1 to 4 mm²)flexible with cable end; Control circuit screw clamp terminals 2 0.00 to 0.00 in² (1 to 2.5 mm²)flexible with cable end; Control circuit screw clamp terminals 1 0.00 to 0.01 in² (1 to 4 mm²)solid; Control circuit screw clamp terminals 2 0.00 to 0.01 in² (1 to 4 mm²)solid; Power circuit EverLink BTR screw connectors 1 0.00 to 0.05 in² (1 to 35 mm²)flexible without cable end; Power circuit EverLink BTR screw connectors 2 0.00 to 0.04 in² (1 to 25 mm²)flexible without cable end; Power circuit EverLink BTR screw connectors 1 0.00 to 0.05 in² (1 to 35 mm²)flexible with cable end; Power circuit EverLink BTR screw connectors 2 0.00 to 0.04 in² (1 to 25 mm²)flexible with cable end; Power circuit EverLink BTR screw connectors 1 0.00 to 0.05 in² (1 to 35 mm²)solid; Power circuit EverLink BTR screw connectors 2 0.00 to 0.04 in² (1 to 25 mm²)solid
Motor Power KW
15 kW at 220 to 230 V AC 50-60 Hz; 22 kW at 380 to 400 V AC 50-60 Hz; 30 kW at 500 V AC 50-60 Hz; 33 kW at 660 to 690 V AC 50-60 Hz; 25 kW at 415 V AC 50-60 Hz; 30 kW at 440 V AC 50-60 Hz
Rated Short Time Withstand Current
400 A 104°F (40°C) - 10 s for power circuit; 810 A 104°F (40°C) - 1 s for power circuit; 84 A 104°F (40°C) - 10 min for power circuit; 208 A 104°F (40°C) - 1 min for power circuit; 100 A - 1 s for signalling circuit; 120 A - 500 ms for signalling circuit; 140 A - 100 ms for signalling circuit
Rated Operational Voltage
Power circuit Less than or Equal to 690 V AC 25 to 400 Hz; Power circuit Less than or Equal to 300 V DC
Flame Retardance
V1 conforming to UL 94
Inrush Power in VA
140 VA 60 Hz cos phi 0.75 (at 68°F (20°C))
Maximum Operating Rate
3600 cyc/h 140°F (60°C)
Mounting Support
Rail; Plate
Control Circuit Type
AC 60 Hz
Ambient Air Temperature For Storage
-76 to 176°F (-60 to 80°C)
Associated Fuse Rating
10 A gG for signalling circuit conforming to IEC 60947-5-1; 100 A gG at Less than or Equal to 690 V coordination type 1 for power circuit; 100 A gG at Less than or Equal to 690 V coordination type 2 for power circuit
Operating Altitude
0 to 9842.52 ft (0 to 3000 m)
Mechanical Robustness
Vibrations contactor open2 Gn, 5 to 300 Hz; Vibrations contactor closed4 Gn, 5 to 300 Hz; Shocks contactor open10 Gn for 11 ms; Shocks contactor closed15 Gn for 11 ms
Fire Resistance
1562°F (850°C) IEC 60695-2-1
Contactor Application
Resistive load; Motor control
Control Circuit Voltage
120 V AC 60 Hz
Product Or Component Type
Reversing contactor
Climatic Withstand
IACS E10; IEC 60947-1 Annex Q category D
Power Pole Contact Composition
3 NO
Protective Treatment
TH IEC 60068-2-30
Minimum Switching Current
5 mA for signalling circuit
Heat Dissipation
4 to 5 W 60 Hz
Device Presentation
Preassembled with reversing power busbar
Conventional Free Air Thermal Current
10 A (at 140°F (60°C)) for signalling circuit; 80 A (at 140°F (60°C)) for power circuit
Product Name
TeSys D; TeSys Deca
Ambient Air Temperature For Operation
-40 to 140°F (-40 to 60°C); 140 to 158°F (60 to 70°C) with derating
Minimum Switching Voltage
17 V for signalling circuit
Utilisation Category
AC-1; AC-3; AC-3e
Country of Origin (subject to change)
France