Item - Relay
General Purpose Relay
Item
General Purpose Relay
AC Contact Rating - Relay
6A @ 277V
DC Contact Rating - Relay
8A @ 28V
Base Type - Plug In Relay
Square
Power Consumption - Relay
1.1 W
Contact Material
Silver Alloy
Body Height - Relay
1.81 in
Body Width - Relay
0.83 in
Body Depth - Relay
1.06 in
Overall Height - Relay
2.17 in
Features
Lockable Test Button; Status LED
Standards
CE Certified, CSA C22.2 No 14, CSA Certified, EN/IEC 61810-1, GOST, Lloyd's, UL 508, UL Listed
Contact Rating
6A @ 277VAC, 8A @ 30VDC
Green Environmental Attribute
RoHS 2011/65/EU Compliant
Status Indicator
LED Indicator, Mechanical Flag
Socket
Mfr. No. RXZE2M114, RXZE2M114M, RXZE2S108M
Mechanical Operating Durability
10,000,000
Series
Harmony(TM) RXM Series
Motor Rated
Not Rated - Not Rated
Resistance Properties
Shock-Resistant, Vibration-Resistant
Horsepower @ 240V AC
Not Rated
Contact Rating (DC)
6 A @ 28V
Electrical Operating Durability
100,000
Dielectric Strength
1,300V AC Between Contacts with Micro Disconnection, 2,000V AC Between Coil and Contact with Basic Insulation, 2,000V AC Between Poles with Basic Insulation
Electrical Connection
Quick-Connect
Push-To-Test Method
Lockable
Minimum Operating Temperature
-40 Degrees F
Contact Rating (AC)
6 A @ 250V
Horsepower @ 120V AC
Not Rated
Minimum Switching Current
10 mA
Maximum Switching Voltage
250V
Maximum Operating Temperature
131 Degrees F
Switching Power
Max 1500 VA/168 W; Min 170 mW 10 mA, 17 V
Switching Voltage
250 V IEC
Operating Temp. Range
-40-55°C
Rated Impulse Withstand Voltage
2.5 kV 1.2/50 µs
Operating Position
Any position
Utilisation Coefficient
0.2
Ambient Air Temperature For Operation
-40 to 131°F (-40 to 55°C)
Rated Insulation Voltage
250 V IEC; 300 V CSA; 300 V UL
Electrical Durability
100000 cycles resistive
Rated Operational Current
3 A 28 V DC) NC IEC; 3 A 250 V AC) NC IEC; 6 A 28 V DC) NO IEC; 6 A 250 V AC) NO IEC; 6 A 277 V AC) UL; 8 A 30 V DC) UL
Drop-Out Voltage Threshold
Greater than or Equal to 0.1 Uc
Continuous Output Current
5 A
Product Certifications
UL; CSA; GOST; CE; Lloyd's
Shock Resistance
10 gnin operation; 30 gnnot operating
Test Levels
Level A group mounting
Minimum Switching Capacity
170 mW 10 mA, 17 V
Maximum Switching Capacity
1500 VA/168 W
Device Presentation
Complete product
Contact Type and Composition
4 C/O
Operating Rate
Less than or Equal to 1200 cycles/hour under load; Less than or Equal to 18000 cycles/hour no-load
Mechanical Durability
10000000 cycles
Vibration Resistance
3 gn +/- 1 mm 10 to 150 Hz)5 cycles in operation; 5 gn +/- 1 mm 10 to 150 Hz)5 cycles not operating
Ambient Air Temperature For Storage
-40 to 185°F (-40 to 85°C)
IP Degree Of Protection
IP40 conforming to IEC 60529
Average Coil Resistance
650 Ohm 20°C +/- 10%
Resistive Rated Load
6 A 250 V AC; 6 A 28 V DC
Control Type
Lockable test button
Rated Operational Voltage Limits
19.2 to 26.4 V DC
Product Or Component Type
Plug-in relay
Control Circuit Voltage
24 V DC
Country of Origin (subject to change)
Indonesia