Item
Enclosed Disconnect Switch
Standards
IEC 60204 || CSA C22.2 No 14 || UL 508 || IEC 60947-4-1
Mechanical Durability
100000 cycles
Electrical Durability
100000 cycles AC-21 || 30000 cycles DC-1...5
Ip Degree Of Protection
IP65 conforming to IEC 60529
Handle Front Plate Colour
yellow
Intermittent Duty Class
30
Tightening Torque
2.1-2.1 N.m screw clamp terminals
[Ithe] Conventional Enclosed Thermal Current
32 A, 32.0 A IEC 690 V || 25 A UL 600 V
Control Type
rotary handle
Fire Resistance
960°C IEC 60595-2-1
Breaking Capacity
320 A 400 V AC-21A) || 320 A 400 V AC-22A) || 320 A 400 V AC-23A)
Rated Operational Power In W
15 kW 400 V AC-23) || 11 kW 400 V AC-3)
[Icm] Rated Short-Circuit Making Capacity
1 kA 400 V at Ipeak
[Ue] Rated Operational Voltage
690 V AC 50/60 Hz
Making Capacity
400 A 400 V AC-21A || 400 A 400 V AC-22A || 400 A 400 V AC-23A
Rotary Handle Padlocking
1 to 3 padlocks 4-8 mm
Performance Level
high performance
Mechanical Robustness
vibrations 10...150 Hz 1 gn) IEC 60068-2-6 || shocks 11 ms 30 Gn) IEC 60068-2-27
Suitability For Isolation
yes
Nema Degree Of Protection
NEMA 12
[Uimp] Rated Impulse Withstand Voltage
8 kV
Product Or Component Type
enclosed emergency stop switch disconnector
Rated Conditional Short-Circuit Current
10 kA 400 V 50 A aM || 10 kA 400 V 50 A gG
[Ie] Rated Operational Current
29 A AC-23A)400 V
Environmental Characteristic
standard environment
Ambient Air Temperature For Operation
-20-50°C
Connections - Terminals
screw clamp terminals 10-10 mm² solid - with cable end || screw clamp terminals 6-6 mm² flexible
[Icw] Rated Short-Time Withstand Current
480 A 400 V 1 s
Rated Power In Hp
5 hp 240 V, UL || 10 hp 480 V, UL || 15 hp 600 V, UL
Conventional Enclosed Thermal Current
32 A
Rated Conditional Short Circuit Current
10 kA 400 V 50 A aM; 10 kA 400 V 50 A gG
Conventional Free Air Thermal Current
32.0 A IEC 690 V; 25 A UL 600 V
Country of Origin (subject to change)
Czechia