Item
Dual Pressure Control
Low Pressure Range (PSIG)
20 in Hg to 100
High Pressure Range (PSIG)
100 to 500
High Pressure Differential (PSIG)
55 psig
Low Pressure Differential (PSIG)
7 to 50
For Use With
Non-Corrosive Refrigerants
Includes
Universal Mounting Bracket
Pressure Connection
36 in Capillary with 1/4 in Flare Nut
Product Type
Dual Pressure Control
Minimum Pressure Range - Low Side
20 in Hg
Application
Air Conditioning, Commercial Refrigeration
Pressure Connection Gender
Female
Maximum Differential Pressure - High Side
Not Applicable
Maximum Differential Pressure - Low Side
50 psi
Reset Type - Low Side
Automatic Reset
Compatible Refrigerant
Non-Corrosive Refrigerants
Capillary Tube Length
36 in
Maximum Pressure Range - High Side
500 psi
Pressure Connection Type
Flare
Minimum Differential Pressure - Low Side
6 psi
Minimum Differential Pressure - High Side
Not Applicable
Pressure Connection Size
1/4 in
Maximum Pressure Range - Low Side
100 psi
Reset Type - High Side
Manual Reset
Switch Action
Open on Fall, Open on Rise
Pressure Type
Differential
Minimum Pressure Range - High Side
100 psi
Contact Rating (AC)
102 A @ 240V AC (Single Phase), 112.2 A @ 208V AC, 15 A @ 220V AC (Three Phase), 15.9 A @ 208V AC, 17 A @ 240V AC (Single Phase), 18.7 A @ 208V AC, 22 A @ 208V AC, 24 A @ 120V AC (Non-Inductive), 24 A @ 208V AC, 24 A @ 220V AC (Three Phase), 24 A @ 240V AC (Single Phase), 90 A @ 220V AC (Three Phase), 95.4 A @ 208V AC, FLA: 24 A @ 120V AC, LRA: 144 A @ 120V AC
Country of Origin (subject to change)
Mexico