Item - Relay
Current Sensing Relay
Input or Control Voltage
21 to 26V AC/DC
AC Contact Rating - Relay
3A @ 250/400V
DC Contact Rating - Relay
0.10A @ 250V, 0.20A @ 125V, 1.00A @ 24V
Sensing Amp Range
0.05 to 15.00A
Core Type - Relay
Internal
Body Depth - Relay
3.58 in
Body Height - Relay
3.62 in
Electrical Connection
Screw Terminal
Body Width - Relay
0.88 in
Status Indicator
No Indicator
Overall Height - Relay
3.62 in
Item
Digital Monitoring Relay
Contact Rating (DC)
0.1 A @ 250V, 0.2 A @ 125V, 1 A @ 24V
Contact Rating (AC)
3 A @ 250/400V, 3 A @ 400V
Minimum Operating Temperature
-13 Degrees F
Maximum Operating Temperature
140 Degrees F
Compatible with Manufacturer Model Number
3UG3522-1AC, 3UG4622-1AA30
Trip Point Type
Adjustable
Adjustment Interface
Digital
Trip Delay Type
Adjustable
Operating Current
0.05-15 A
Electrical Operating Durability
100,000
Standards
CCC, CS, EAC, RCM, UL Listed
Monitored Parameters
Overcurrent, Undercurrent
Mechanical Operating Durability
10,000,000
Compatible Manufacturer Part Number
3UG3522-1AC, 3UG4622-1AA30
Compatible with Manufacturer Part Number
3UG3522-1AC, 3UG4622-1AA30
Compatible with Manufacturer Model Number [NEW]
3UG3522-1AC, 3UG4622-1AA30
Compatible Manufacturer Model Number
3UG3522-1AC, 3UG4622-1AA30
For Use with Mfr. Model Number
3UG3522-1AC, 3UG4622-1AA30
For Use With Mfr. Model Number
3UG3522-1AC, 3UG4622-1AA30
function direct current window present
Yes
direct voltage undercurrent possible
Yes
Max. rated DC voltage for controls
24 volt
Min. response delay
0.1 second
Lowest value of measurement range for current
0 ampere
Design of electrical connection
Screw connection
direct voltage overcurrent possible
Yes
Max. rated AC voltage for controls, 50 Hz
26.4 volt
min. rated control voltage Us with DC
24 volt
min. rated control voltage Us with AC 50 Hz
20.4 volt
Max. response delay
20 second
detachable terminals present
Yes
1 phase low current possible
Yes
1-phase overload current possible
Yes
max. rated AC voltage for controls (60 Hz)
26.4 volt
min. rated control voltage Us with AC 60 Hz
20.4 volt
Greatest value of measuring range for current
15 ampere
Country of Origin (subject to change)
Germany