Item
Auxiliary contact block
Standards
IEC 60947-3, UL 508, CSA C22.2 No 14, IEC 60947-5
Use
Auxiliary Contact Block
Mounting Location
right || left
[Ue] Rated Operational Voltage
690 V AC 50/60 Hz
[Ie] Rated Operational Current
6 A AC-15)24 V AC || 6 A AC-15)48 V AC || 6 A AC-15)127 V AC || 3 A AC-15)240 V AC || 3 A DC-13)24 V DC || 1.5 A DC-13)48 V DC || 0.55 A DC-13)127 V DC || 0.27 A DC-13)240 V DC
Contacts Type And Composition
1 NC + 1 NO
Performance Level
high performance
Contact Operation
simultaneous 1 NC || simultaneous 1 NO
Fire Resistance
850°C IEC 60695-2-11
Product Certifications
cULus || GL
Network Frequency
50/60 Hz
[Ithe] Conventional Enclosed Thermal Current
10 A
Mechanical Robustness
vibrations 2 to 100 Hz Fc 0.7 g) IEC 60068-2-6 || shocks 11 ms Ea 15 gn) IEC 60068-2-27
Connections - Terminals
control circuit screw clamp terminals 2.5-2.5 mm² flexible - without cable end
Product Or Component Type
auxiliary contact block
Minimum Output Voltage
5 V
Minimum Output Current
10 mA
Ambient Air Temperature For Operation
-25-55°C
Tightening Torque
control circuit 0.8-1 N.m screw clamp terminals
Ip Degree Of Protection
IP20 conforming to IEC 60529
[Uimp] Rated Impulse Withstand Voltage
8 kV
[Ith] Conventional Free Air Thermal Current
10 A 55°C
Range Compatibility
TeSys (TeSys VARIO LS) VLSA || TeSys (TeSys VARIO LS) VLS3P || TeSys (TeSys VARIO LS) VLS1P
Rated Operational Current
6 A AC-15)24 V AC; 6 A AC-15)48 V AC; 6 A AC-15)127 V AC; 3 A AC-15)240 V AC; 3 A DC-13)24 V DC; 1.5 A DC-13)48 V DC; 0.55 A DC-13)127 V DC; 0.27 A DC-13)240 V DC
Conventional Free Air Thermal Current
10 A (at 131°F (55°C))
Conventional Enclosed Thermal Current
10 A
Country of Origin (subject to change)
Italy