Item
Air Velocity Transmitter
Air Velocity Accuracy
+/-3% (32 to 122 Degrees F)
Velocity Ranges
FPM: 250, 500, 1000, 2000, 3000, 5000, 10000, 15000
Velocity Accuracy
3% FS Process gas: 32 to 122 Degrees F (0 to 50 Degrees C); 4% FS Process gas: -40 to 32 Degrees F u0026 122 to 212 Degrees F (-40 to 0 Degrees C u0026 50 to 100 Degrees C)
Power Required
10 to 16 VAC 1.5A Rating Required on Supply Due to Initial Power Surge Drawn by Transmitter, 12 to 35 VDC
Response Time (Sec.)
1.5 Seconds to 95% of Final Value (Output Filter Set to Minimum)
Operating Temp.
Process: -40 to 212 Degrees F (-40 to 100 Degrees C) Ambient: 32 to 140 Degrees F (0 to 60 Degrees C)
Max. Pressure (PSI)
100 psi
Manufacturers Warranty Length
1
Maximum Feet Per Minute
15000 FPM
Minimum Operating Temperature
32 Degrees F
Digital Display Screen Type
No Display
Minimum AC Voltage Required
10 V
Maximum Probe Length
24 in
Maximum DC Voltage Required
35 V
Minimum DC Voltage Required
12 V
Maximum Velocity Measured
15,000 fpm
Maximum AC Voltage Required
16 V
Minimum Velocity Measured
250 fpm
Maximum Operating Temperature
140 Degrees F
Maximum Output Signal
20 mA
Minimum Temperature Measured
-40 Degrees F
Manufacturer Warranty Length
1 yr
Maximum Temperature Measured
212 Degrees F
Minimum Output Signal
4 mA
Country of Origin (subject to change)
United States