HP @ 3 Phase - 480V
125 hp
Aux. Contact Configuration
1NO/1NC
Control Circuit Voltage Limits
0.85 to 1.1 Uc
Mechanical Durability
5 Mcycles
Thermal Amperage
275 A (at 40°C)
Hold VA
35 VA (at 50 Hz), 40 VA (at 60 Hz)
Rated Short-Time Withstand Current
1500 A (at 40°C for 10 s), 320 A (at 40°C for 15 min), 800 A (at 40°C for 1 min), 2000 A (at 40°C for 1 s), 1000 A (at 40°C for 30 s)
Impulse Withstand Voltage
8 kV
Operating Time
5 to 10 ms (Coil De-energization and NC Contact Closing), 9 to 13 ms (Coil De-energization and NO Contact Opening), 8 to 22 ms (Coil Energization and NC Contact Opening), 13 to 27 ms (Coil Energization and NO Contact Closing)
Electrical Connection
Bars
Rated Insulation Volts
600/1000V
Max. Operating Watts
55 kW (at 220/230/240V), 90 kW (at 380/400V, 415V, 440V), 110 kW (at 500V), 132 kW(at 690V)
Country of Origin (subject to change)
Unknown